150kVA PERKINS Engine - 1106A-70TAG2
TOTAL POWER RANGE
| Gross Mechanical Output | 140-204 kWm | 
| Typical Electrical Output | 150-220 kVA (120-176 kWe) | 
| Rated Speed | 1500/1800 rpm | 
50 HZ TYPICAL ELECTRICAL OUTPUT
| Prime | 150.0-200 kVA | 
| Standby | 165.0-220 kVA | 
60 HZ TYPICAL ELECTRICAL OUTPUT
| Prime | 132.0-156.8 kWe | 
| Standby | 146.5-173 kWe | 
EMISSION STANDARDS
| Emissions | Fuel Optimised | 
GENERAL
| Number of Cylinders | 6 vertical inline | 
| Bore | 105 mm | 
| Stroke | 135 mm | 
| Displacement | 7.01 l | 
| Compression Ratio | 16:1-18.2:1 | 
| Aspiration | Turbocharged aftercooled | 
| Combustion System | Direct injection | 
| Rotation from Flywheel End | Anti-clockwise | 
| Cooling System | Liquid | 
| Aftertreatment | - | 
| Typical Alternator Efficiency | 91-92% | 
| Switchable | Yes | 
ELECTROPAK DIMENSIONS
| Length | 1706 mm | 
| Width | 756 mm | 
| Height | 1092 mm | 
| Dry Weight | 743 kg | 
DISCLAIMER
| Note 1 | *Final dimensions dependent on selected options | 
DEFINITIONS
| Prime Power | Unlimited hours usage, with an average load factor of 80% over each 24 hour period. A 10% overload is available for 1 hour in every 12 hours operation. | 
| Standby Power | Limited to 500 hours annual usage, with an average load factor of 80% of the published standby power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously. No overload is permitted on standby power. | 
 
 
	 
					 
					 
					 
					 
	
 
				 
				 
					 
					 
					 
					 
		 
		 
		 
		 
		 
		 
		